Hp Anab EQ5 Manual do Utilizador Página 51

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 131
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 50
EQ5 AC Drive Operations Manual
_______________________________________________________________________
TECO – Westinghouse Motor Company Parameters A01 – A18 ~ U01 – U89 45
A Parameters
Para.
No.
NAME LCD Display Setting range Unit
Min.
Unit
Factory setting
Change
During
Oper.
User
Set
value
Remark
30HP
/
CT
40HP/VT
40HP
/
CT
50HP/VT
A01 Maximum frequency 2 A01 MAX Hz-2 50 to 120Hz Hz 1 60 N
A02 Base frequency 2 A02 BASE Hz-2 25 to 120Hz Hz 1 60 N
A03 Rated voltage 2 (at Base frequency 2 ) A03 RATED V-2
0:
V 1
220: (230V class)
N
80 to 240V: (230V class) 380: (460V class)
320 to 480V: (460V class)
A04 Maximum voltage 2 (at Base frequency 2) A04 MAX V-2
80 to 240V: (230V class)
V 1
220:(230V class)
N
320 to 480V: (460V class) 380:(460V class)
A05 Torque boost2 A05 TRQ BOOST2 0.0, 0.1 to 20.0 - - 0.1 Y
A06 Electronic thermal overload relay for motor 2 A06 ELCTRN OL2 0, 1, 2 - - 1 Y
A07 (Level) A07 OL LEVEL2 INV rated current 20%to135% A 0.01 Motor rated current Y
A08 (Thermal time constant) A08 TIME CNST2 0.5 to 75.0 min min 0.1 5.0 10.0 Y
A09 Torque vector control 2 A09 TRQVECTOR2 0, 1 - - 0 N
A10 Number of motor-2 poles A10 M2 POLES 2 to 14 poles poles 2 4 N
A11
Motor 2
(Capacity)
A11 M2-CAP
Up to 30HP:0.01 to 60HP
HP 0.01 Motor capacity N
40HP and above:0.01to800HP
A12 (Rated current) A12 M2-Ir 0.00 to 2000A A 0.01 Motor rated current N
A13 (Tuning) A13 M2 TUN1 0, 1, 2 - - 0 N
A14 (On-line Tuning) A14 M2 TUN2 0, 1 - - 0 N
A15 (No-load current) A15 M2-Io 0.00 to 2000A A 0.01 TWMC standard rated value N
A16 (%R1 setting) A16 M2-%R1 0.00 to 50.00% % 0.01 TWMC standard rated value Y
A17 (%X setting) A17 M2-%X 0.00 to 50.00% % 0.01 TWMC standard rated value Y
A18 (Slip compensation control 2) A18 SLIP COMP2 0.00 to 15.00Hz Hz 0.01 0.00 Y
U Parameters
U01 Maximum compensation frequency U01 USER 01 0 to 65535
- 1
75 A
during braking torque limit
U02 1st S-shape level at acceleration U02 USER 02 1 to 50% % 1 10 NA
U03 2nd S-shape level at acceleration U03 USER 03 1 to 50% % 1 10 NA
U04 1st S-shape level at deceleration U04 USER 04 1 to 50% % 1 10 NA
U05 2nd S-shape level at deceleration U05 USER 05 1 to 50% % 1 10 NA
U08
Main DC link
capacitor
(Initial value) U08 USER 08 0 to 65535 - 1 xxxx A
U09 (Measured value) U09 USER 09 0 to 65535 - 1 0 A
U10 PC board capacitor powered on time U10 USER 10 0 to 65535h h 1 0 A
U11 Cooling fan operating time U11 USER 11 0 to 65535h h 1 0 A
U13 Magnetize current vibration damping gain U13 USER 13 0 to 32767 - 1 819 410 A
U15 Slip compensation filter time constant U15 USER 15 0 to 32767 - 1 556 546 A
U23 Integral gain of continuous operation U23 USER 23 0 to 65535
- 1
1738 1000 A
at power failure
U24 Proportional gain of continuous U24 USER 24 0 to 65535
- 1
1024 1000 A
operation at power failure
U48 Input phase loss protection U48 USER 48 0, 1, 2
- -
-75HP 100HP- NA
0 1
U49 RS-485 protocol selection U49 USER 49 0, 1 - - 1 NA
U59
Braking-resistor function select(up to 30HP/CT,
40HP/VT)
U59 USER 59
00 to A8(HEX)
- 1
00 NA
Manufacturer's function(40HP/CT, 50HP/VT or
more)
U60 Regeneration avoidance at deceleration U60 USER 60 0, 1
- -
0 NA
U61 Voltage detect offset and gain adjustment U61 USER 61 --30HP/CT, 40HP/VT0 (Fixed.)
- -
0 A
40HP/CT, 50HP/CT--0, 1, 2
U89 Motor overload memory U89 USER 89 0.1 - - 1 A
retention
NOTES
Vista de página 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 130 131

Comentários a estes Manuais

Sem comentários