Hp Parallel Uninterruptible Power System Manual do Utilizador Página 76

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 75
Communication 76
Pin number Signal name Function Direction from the UPS
4
No connection
5
GND Signal common (tied to chassis)
6
No connection
7
No connection
8
No connection
9
No connection
Control terminals
The cables should be connected to the control terminal with a mating connector. Input and output terminals
have a functional isolation from terminal to terminal. They are connected to the UPS chassis through
individual 1 MW resistors.
If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control
is preferred.
Relay output contacts
WARNING: The relay output contacts must not be connected to any utility connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of
30 VAC/1 A and 60 Vdc/2 A nominal values.
Vista de página 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 114 115

Comentários a estes Manuais

Sem comentários