
Web interface 14
Indicators Meaning
Actual operator display alarm
message
Water Temp. Out Failed
Actual web interface alarm
message
Water Unit Temperature Output Out of Range
Condition Water temperature sensor is not working properly (possible open circuit)
Sensors Water group sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Verify the water supply.
2. Verify whether the water temperature is below or above the water temperature expected range.
3. Contact your building supervisor.
4. Contact HP, or see the HP website (http://www.hp.com).
Water flow sensor is not working properly
Indicators Meaning
Actual operator display alarm
message
Water flow Sensor ?
Actual web interface alarm
message
Water flow Sensor Value Out of Range
Condition Water flow sensor is not working properly
Sensor Water group
SNMP notification Warning
Type of message Warning
Solution:
1. Verify the water supply.
2. Contact HP, or see the HP website (http://www.hp.com).
Water flow valve is closed
Indicators Meaning
Actual operator display alarm
message
Water Valve ?
Actual web interface alarm
message
Water Valve Failed
Condition Water flow valve is closed and water flow is detected
Modules Water group
SNMP notification Warning
Type of message Warning
Solution:
Comentários a estes Manuais