Web interface 19
3.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT: Use caution when entering temperatures in the Emergency Door Opening fields.
Setting the temperature thresholds too low might cause the MCS unit to shut down.
The condensation pump has exceeded x cycles
Indicators Meaning
Actual operator display alarm
message
Excessive Moisture
Actual web interface alarm
message
The condensation pump has exceeded x cycles
Condition The water level has exceeded the permissible level of the condensation
pump sensor
Modules or sensors Condensation pump sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Look for leaks or determine if condensation is the cause.
2. If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles
Warning Threshold field.
IMPORTANT: Use caution when entering temperatures in the Condensation Pump Threshold
fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.
Default settings will vary, depending on the humidity level of your data center and the heat
load generated by the equipment in the MCS.
The condensation pump has run more than x seconds
Indicators Meaning
Actual operator display
alarm message
Excessive Moisture
Actual web interface
alarm message
The condensation pump has run more than x seconds
Condition The water level has exceeded the permissible level of the condensation pump sensor.
Modules or sensors Condensation pump sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Look for leaks or determine if condensation is the cause.
2. If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running
Time Warning Threshold field.