Verify the water valve is closed.
2. Contact HP, or see the HP website (http://www.hp.com).
Leak detector sensor is not working properly
Indicators Meaning
Actual operator display alarm
message
Leak detector?
Actual web interface alarm
message
Leak detector Failed
Condition Leak detector sensor is not working properly
Sensors Leak detector sensor
SNMP notification Warning
Type of message Warning
Solution:
Contact HP, or see the HP website (http://www.hp.com
).
Uneven heat load
Indicators Meaning
Actual operator display alarm
message
Heat Load?
Actual web interface alarm
message
Heat Load Warning
Condition Measured air temperature values dramatically different from top to bottom
Sensors Air temperature sensors
SNMP notification Warning
Type of message Warning
Solution:
1. Verify that nothing is blocking the heat path.
2. Verify that the server is loading.
3. Adjust the Temperature Difference for Heat Load Warning in the Advanced tab (on page 29).
Heat overload condition (High Temperature Threshold field)
Indicators Meaning
Actual operator display alarm
message
Temperature Warning
Actual web interface alarm
message
Temperature Warning
Condition Heat overload condition
Modules or sensors Average server air temperature is above the temperature assigned in the
web interface Intake Temp tab High Temperature Threshold field
SNMP notification Critical
Type of message Alarm