3 bulk power supplies.
Typical power consumption: 1870 VA (9.35 A @ 200 VAC across 2 cords)
Power Distribution
Units
60 amp Power Distribution Unit
AF916A (NA/JPN) and AF917A (International)-supported with 10K G2 rack
E7683A (US) and E7684A (International)-supported in Rack System E
A 60 amp Power Distribution Unit (PDU) has been developed for Integrity customers that prefer to
use fewer, higher amperage connections into their wall electrical infrastructure. This PDU is sold
separately and can be ordered with any HP Server solution. For more details on PDUs, please
refer to the PDU sales collateral.
The drawing below is an example of how the PDU can be configured with the HP 9000 rp8440
Server in a dual grid configuration. In this case there are two HP 9000 rp8440 servers (average
configurations drawing ~9 amps each) and two 60 amp PDUs configured with redundant power.
The blue cords represent the primary power connections needed for normal operation. In this
example, cords from each server are plugged
into a separate branch circuits. However, it is acceptable, for lower VA configurations, for each
server to plug both grid A cords into one branch circuit and both grid B cords into second branch
circuit. The remaining PDU outlets can be used to power other components as long as the
specifications for the PDU rating are not exceeded.
For redundant power inputs, the second set of red cords is added. If the second PDU is plugged
into a second grid this configuration provides protection against:
Losing power from a single power grid
Accidental tripping of one or two circuit breakers
Accidental disconnect of a single PDU power cord
Accidental disconnect of up to four system power cords
30 amp Power Distribution Unit-
252663 D74 (NA/JPN) and 252663 B33 (International)-supported on 10K G2 rack
E7681A (NA/JPN) and E7682A (International)-supported on Rack System E
A 30 amp Power Distribution Unit (PDU) is also supported with HP 9000 rp8440 Server. This PDU
is sold separately and can be ordered with any HP Server solution.
The following configuration guidelines apply when using the 30 amp PDU:
HP 9000 rp8440 Server plugs A0 and A1 should be plugged into the same PDU
Ax and Bx cords should never be plugged into the same PDU
Use two 30 amp PDUs to achieve input power redundancy. A0/A1 and B0/B1 into separate
PDUs.
Ordering tools will not force the purchase of a second PDU for input power redundancy. A
second PDU must be manually selected if redundant input power is desired.