HP 460W Common Slot Platinum Hot Plug Power Supply Kit
Part Number
593188-B21
Input Voltage Range (Vrms)
100 to 240
Frequency Range (Nominal) (Hz)
50/60
Nominal Input Voltage (Vrms)
100 120 208 200 220 230 240
Maximum Rated Output Wattage
460 460 460 460 460 460 460
Nominal Input Current (A rms)
5.3 4.3 2.5 2.4 2.3 2.2 2.1
Max Rated Input Wattage Rating
(Watts)
512 505 493 493 492 492 491
Max. Rated VA (Volt-Amp)
526 518 506 506 505 505 504
Efficiency (%) at Max. Rated Output
Wattage
89.8 91.2 93.2 93.3 93.5 93.6 93.6
Power Factor
0.985
Leakage Current (mA)
0.42 0.50 0.83 0.87 0.92 0.96 1.00
Max. Inrush Current (A peak)
30
Max. Inrush Current duration (mS)
20
Maximum British Thermal Unit
Rating (BTU-Hr)
1747 1722 1683 1682 1679 1678 1677
HP 750W Common Slot Platinum Hot Plug Power Supply Kit
Part Number
593831-B21
Input Voltage Range (Vrms)
100 to 240
Frequency Range (Nominal) (Hz)
50/60
Nominal Input Voltage (Vrms)
100 120 208 200 220 230 240
Maximum Rated Output Wattage
750 750 750 750 750 750 750
Nominal Input Current (A rms)
8.6 7.1 4.2 4.0 3.8 3.6 3.4
Max Rated Input Wattage Rating
(Watts)
841 828 809 808 807 806 805
Max. Rated VA (Volt-Amp)
863 850 830 829 828 827 826
Efficiency (%) at Max. Rated Output
Wattage
89.2 90.6 92.7 92.8 93.0 93.1 93.2
Power Factor
0.985
Leakage Current (mA)
0.42 0.50 0.83 0.87 0.92 0.96 1.00
Max. Inrush Current (A peak)
30
Max. Inrush Current duration (mS)
20
Maximum British Thermal Unit
Rating (BTU-Hr)
2868 2825 2761 2757 2753 2749 2747