Trap name OID () Caused by Cleared by New in
revision 5.0
CpqRPMTrapCMCVoltNormal 10013 — — —
CpqRPMTrapCMCHmdtUnder 10021 — 10023 —
CpqRPMTrapCMCHmdtOver 10022 — 10023 —
CpqRPMTrapCMCHmdtNormal 10023 — — —
cpqRPMTrapCMCSmokeDetecte
d
10031 — 10032 —
cpqRPMTrapCMCSmokeCleared 10032 — — —
cpqRPMTrapCMCShockDetected 10041 — 10042 —
CpqRPMTrapCMCShockCleared
cpqRPMTrapCMCAux1Alarm 10051 — 10052 —
cpqRPMTrapCMCAux1Cleared 10052 — — —
cpqRPMTrapCMCAux2Alarm 10053 — 10054 —
cpqRPMTrapCMCAux2Cleared 10054 — — —
cpqRPMTrapCMCInput1Opened
cpqRPMTrapCMCInput1Closed 10102 — — —
cpqRPMTrapCMCInput2Opened 10103 — 10104 —
cpqRPMTrapCMCInput2Closed 10104 — — —
cpqRPMTrapCMCInput3Opened 10105 — 10106 —
cpqRPMTrapCMCInput3Closed
cpqRPMTrapCMCInput4Opened 10107 — 10108 —
cpqRPMTrapCMCInput4Closed 10108 — — —
cpqRPMTrapCMCLockset1Unloc
ked
10111 — 10114 —
cpqRPMTrapCMCLockset1Failed
ToLock
10112 — 10114 —
cpqRPMTrapCMCLockset1Error 10113 — 10114 —
cpqRPMTrapCMCLockset1Locke
d
10114 — — —
cpqRPMTrapCMCLockset2Unloc
ked
10116 — 10119 —
cpqRPMTrapCMCLockset2Failed
ToLock
10117 — 10119 —
cpqRPMTrapCMCLockset2Error 10118 — 10119 —
cpqRPMTrapCMCLockset2Locke
d
10119 — — —
cpqRPMTrapCMCLockset1Norm
al
10134 — — —
cpqRPMTrapCMCLockset2Norm
al
10135 — — —
cpqRPMTrapUPSInputVoltageBel
owMin
20001 — 20003 —
cpqRPMTrapUPSInputVoltageAb
oveMax
20002 — 20003 —
cpqRPMTrapUPSInputVoltageNo
rmal
20003 — — —
cpqRPMTrapUPSOutputVoltageB
elowMin
20011 — 21020 —