Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Product Specification: Model C200 - Capstone MicroTurbine
460045 Rev C (November 2008) Page 11 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Fuel Input Requirements at Full Load Power
Table 5 presents fuel input requirements at full load power and ISO conditions.
Table 5. Fuel Input Requirements
C200 Version
Inlet Pressure
Range
Fuel Type
Fuel Energy Content
Range [HHV]
High Pressure NG
75 - 80 psig
(517 – 552 kPaG)
Low Pressure NG
0.25 – 5 psig
(1.8 – 103 kPaG)
Natural Gas
30,700 – 47,500 kJ/m
3
(825 – 1,275 Btu/scf)
Landfill
75 – 80 psig
(517 – 552 kPaG)
Landfill Gas
13,000 – 22,300 kJ/m
3
(350 – 600 Btu/scf)
Digester
75 – 80 psig
(517 – 552 kPaG)
Digester Gas
20,500 – 32,600 kJ/m
3
(550 – 875 Btu/scf)
Notes:
(1) Minimum power output is 100kW for these fuels. Additional fuel gas conditioning will be required.
Consult Capstone for specific application guidance.
Exhaust Output Ratings at Full Load Power
Table 6 presents nominal exhaust output ratings at full load power and ISO conditions.
Table 6. Exhaust Output Ratings
Parameter
C200 CARB
Natural Gas
All Other C200
Nominal Exhaust Gas Temp
(1)
280 °C (535 °F) 280 °C (535 °F)
Nominal Total Exhaust Energy
(1)
1,420,000 kJ/hr
(1,350,000 Btu/hr)
1,420,000 kJ/hr
(1,350,000 Btu/hr)
NOx Emissions
(2)
<4 ppm V
@ 15% O
2
<9 ppm V
@ 15% O
2
Exhaust Mass Flow
1.33 kg/s
(2.93 lbm/s)
1.33 kg/s
(2.93 lbm/s)
Notes:
(1) These are the final exhaust temperature and exhaust energy if the external heat recovery module is bypassing
exhaust heat. Temperature and exhaust energy will be lower while recovering heat.
(2) Emissions for standard natural gas at 1,000 BTU/scf (HHV).