Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Product Specification: Model C200 - Capstone MicroTurbine
460045 Rev C (November 2008) Page 5 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Performance Specification
Performance Ratings at Full Load Power
Table 2 summarizes performance ratings at full load power and ISO conditions.
Table 2. Performance Ratings
Parameter C200 Low Pressure NG All Other C200
Net Power Output
190 (+0/- 4) kW net 200 (+0/- 4) kW net
Net Efficiency (LHV)
31 (± 2)% 33 (± 2)%
Nominal Net Heat Rate
(LHV)
11,600 kJ/kWh
(11,000 Btu/kWh)
10,900 kJ/kWh
(10,300 Btu/kWh)
Nominal Generator Heat
Rate (LHV)
10,700 kJ/kWh
(10,200 Btu/kWh)
10,200 kJ/kWh
(9,700 Btu/kWh)
Nominal Steady State
Fuel Flow (HHV)
(1) (2)
2,400,000 kJ/hr
(2,280,000 BTU/hr)
2,400,000 kJ/hr
(2,280,000 BTU/hr)
Notes:
(1) The ratio of Higher Heating Value (HHV) to Lower Heating Value (LHV) is assumed to be 1.1.
(2) Onload fuel flows can be up to two times higher than the steady state values.
Electrical Performance Ratings at Full Load Power
Table 3 presents the electrical performance ratings for Model C200 MicroTurbines operating
in the Grid Connect mode at ISO conditions with zero back pressure.
Table 3. Electrical Performance Ratings in Grid Connect Mode
Parameter C200 Low Pressure NG All Other C200
Net Power Output
190 (+0/- 4) kW 200 (+0/- 4) kW
Max Apparent Power
Output
(1)
190 kVA 200 kVA
Nominal Voltage
Operating Range
400 to 480 VAC 400 to 480 VAC
Nominal Frequency
Operating Range
50/60 Hz 50/60 Hz
Output
Voltage Connection
(2)
3-phase, 3 or 4 wire wye 3-phase, 3 or 4 wire wye
Max Output
Current Steady State
275 Amps RMS @ 400V
230 Amps RMS @ 480V
290 Amps RMS @ 400V
240 Amps RMS @ 480V
Current THD
IEEE 519 compliant, 5% IEEE 519 compliant, 5%
Notes:
(1) The microturbine system operates at unity power factor in Grid Connect mode.
(2) The grid connection to the microturbine must be neutral grounded.