2-14
Installing the Switch
Installation Procedures
Installing the Switch
5. Connect the power cords to the switch and route the cords through the
rack.
a. Connect each power cord to a power supply and secure the cord with
a velcro strap. Route each cord through the rack.
b. Install the air plenum in a power-side mounting.
Caution Make sure the air flow is not restricted in the front or back of the switch. Figure
2-1 on page 2-8 shows the default air flow direction from power to ports.
If you are installing a 6600 Switch with the port side facing the cold aisle,
no air plenum is necessary. Continue with Step 6.
If you are installing a 6600 Switch with the power side facing the cold aisle,
an air plenum is necessary. Use the correct plenum for the size of the
switch being installed. The plenum comes in two sizes. Both plenums are
installed in the same way.
J9480A is the shorter air plenum for 6600-24XG, 6600-48G, and
6600-48G-4XG Switches.
J9481A is the longer air plenum for 6600-24G and 6600-24G-4XG
Switches.
After you connect and route the power cords, slide the plenum into the
rails until the plenum is fully inserted and the two mounting holes align
with the mounting holes on the bracket and rack.
Figure 2-9. Installing an Air Plenum
In a power-side mounting, slide
the plenum into the rails.
Power-side mounting for a 6600 Switch
(Option 1 or 2)