23
Table 5: Tate All Steel 1250 raised floor specifications
Item Rating
Dead load 34.2 kg/m
2
(7 lb/ft
2
)
Design load
1
567 kg (1,250 lb)
Rolling load 227 kg (500 lb)
1
Similar to concentrated load
Note:
The IT rack of the MCS 5042 can carry a static load of up to 1,360 kg
(3,000 lb).
Note:
In Figures 13 and 14, the load is in the center of the IT racks. Due to
adjacency, the leveling feet in points B and E in Figure 13 and points B, C,
F, and G in Figure 14 are combined to one concentrated weight.
Figure 13: Weight distribution on the leveling feet locations in a single rack configuration