38
Figure 27: Recommended floor cutouts (single rack configuration)Option 2 (MCS 5042 rack side flush to tile)
Note:
The wider opening in the back of the IT rack is optional.
Note:
The floor tile sizes used in Figure 27 are 600 mm x 600 mm (23.6 inches x
23.6 inches). Floor tile sizes vary.
Note:
The allowable tolerances are +/- 3.2 mm (+/- 0.125 inches). When
installing multiple MCS 5042 units in a row, you must consider the
tolerances as you plan the cutouts.