HP Modular Cooling System Manual de Instalação Página 30

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 60
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 29
30
Figure 20 illustrates the MCS 5042 being supplied directly by a dedicated chiller unit or water-to-
water heat exchanger in a closed loop configuration.
Figure 20: Dedicated chiller unit directly supplying the MCS 5042
Plumbing considerations
A number of plumbing factors must be considered when installing the MCS 5042:
(Highly recommended) Installing water shut off valves to enable infrastructure system flushing for the
inlet and outlet of each MCS 5042
Flow rate and pressure capacity of chilled water plant input to the design of the facility feed line
and dedicated water loop pipe diameters
Material compatibility within piping system to minimize the potential for electrochemical corrosion
and must be corrosion-resistant
Minimization of elbows and other restrictions that increase flow resistance
Insulation of piping to minimize risk of condensation and reduce incidental heating of supplied
chilled water
Availability of a floor drain or reclamation system to capture system condensation
Structural securing of piping to support weight of distribution network filled with water
Water quality management, including particulate filtration, treatment, and flushing provisions, with
isolation valves for service requirements
Availability and access to a data center leak detection system to monitor the infrastructure system
for leaks
Air vents installed at the highest point in the pipe system (Each MCS 5042 has an air vent, but
additional vents in the supply piping system must be considered.)
Vista de página 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 59 60

Comentários a estes Manuais

Sem comentários