You must perform several steps to determine the coolant requirements and corresponding resources
necessary for effective implementation of the MCS 5042. The flowchart in Figure 31 outlines the steps
and necessary information/resources for each aspect of the implementation.
Figure 31: Coolant implementation flow chart for one rack
Cooling loop sizing
Sizing the cooling loops can be straight forward based on the planned cooling requirements of each
populated/planned MCS 5042 server enclosure. The amount (watts) of heat to be removed from each
component in the server rack must be added together for the total heat to be removed by the MCS
5042 cabinet. You can copy Table 9 for documenting individual cabinet calculations. Calculations
must include the equipment installed today and additional equipment planned for installation over the
design life of the system.