An HP Water Hook Up Kit must be installed prior to activating an MCS 5042. The length is
approximately 350 cm (138 inches) of flexible hose terminated with fittings at each end. The length
that is available outside the MCS 5042 depends on the type of connection that is desired as shown in
Figure 22.
Table 6: Available hose lengths outside the MCS 5042 by connection type
Connection type Approximate length supply hose Approximate length return hose
Bottom 280 cm (110 inches) 300 cm (118 inches)
Rear 280 cm (110 inches) 300 cm (118 inches)
Top 200 cm (79 inches) 180 cm (71 inches)
Figure 23 shows the location of the condensate (blue) and overflow (red) in the rear of the cooling
unit. The MCS 5042 includes both tubes for the hook up. Each tube is approximately 3 m (9 feet) in
length. The overflow hose has an inner diameter of 9 mm (0.35 in) and
the condensation hose
has a
n outer diameter of 8 mm (0.31 in). The preferred method of routing for all hoses is downward
at an angle of at least 3º (pitch of 0.6 inches per 12 inches), without loops, and away from the MCS
5042 cabinet. Pumped condensation and gravity-fed overflow hoses must be routed to a floor drain
or reclaim system.
Figure 23: MCS 5042 condensation and overflow hook up
Note:
Flexible attachment hoses are intended to allow for deflection in any
direction for equipment mounted on dynamic platforms, or for slight
relocation of cabinets.