HP Modular Cooling System Guia de Início Rápido Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 93
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
Overview 13
Fan controllerOperates the fans, according to the cabinet air temperature
Air bleeder valveEnables air to manually bleed out of the system when coolant is initially filled
Water controllerSenses condensation, leaks, water temperatures, flow rate, and the status of the
water valve, and sends this data to the management module
AC input/network connectionProvides primary and secondary AC input connections, if available,
and a network management interface
AC transfer switchProvides dual-AC power with a fail-over feature for redundancy
FansProvide circulation of cooled air through the computer equipment rack
Water groupIncludes the water valve, flow meter, check valve, and temperature sensors
A condensation pump with overflow and condensation lines connects to the water group.
Each MCS-200/100 has one water group.
MCS-100 components
The MCS-100 is an air and water heat exchanger that removes high levels of excess heat generated by
equipment installed in HP racks. The installed equipment pulls cold air in through the front of the closed
MCS-100 and uses that air for internal cooling. After the air is warmed, the MCS-100 expels the air through
the rear vents.