Facility planning for implementation 69
Item Description Specifications
6
Strainer isolation valves Valve type: 31.75-mm (1.25-inch), two-piece, full-port, brass ball valve,
with chrome plated brass ball, PTFE seats, steel handle, with solder end
connections.
Pressure rating: 600 psi WOG, 150 psi WSP
Orientation: Stem vertical up for lateral level operation. Offset valves on
CHWS and CHWR piping to prevent interference from lever actuators
when closed.
Watts FBVS-3C or equivalent
typical 4
7
Strainer Type: 31.75-mm (1.25-inch) wye-patterned bronze strainer, with #30
stainless steel wire mesh liner, ¾-inch tapped retainer cap & gasket,
and solder end connections. Provide 19.05 mm (0.75 inch) ball valve
for blowdown with cap and chain.
Pressure rating: 400 psi WOG, 125psi WSP
Orientation: with basket and blowdown valve directed down
Watts S777 or equivalent
8
System drain valve Type: 19.05-mm (0.75-inch) two-piece, full-port, brass ball valve with
chrome plated brass ball, PTFE seats, and steel handle, with threaded
connections.
Pressure rating: 600 psi WOG, 150 psi WSP
Watts FBV-3C or equivalent
9
Nipple Type: 19.05-mm (0.75-inch) brass close nipple
10
Cap Type: 19.05-mm (0.75-inch) brass cap with chain
11
Hose Type: 1.25-inch flexible hose supplied with MCS-200/100 Water
Hook-up Kit.
12
Condensate line Pipe: 19.05-mm (0.75-inch) copper or Schedule 40 PVC
Fittings: Wrought Copper or Schedule 40 PVC
Orientation: Sloping downward in a minimum angle of 1º (0.25 inch
per 1 ft) and away from the MCS 5042 for gravity drain
13
Compression fitting Type: 6.35-mm (0.25-inch) male NPT X 8 mm (0.31-inch) compression
fitting, Parker Hannifin, FBMB8-1/4 Metrulok fitting, Festo
QB-1/4-5/16-U or equivalent and installed by plumbing contractor,
typical 1
14
Hose barb Type: 12.7-mm (0.50-inch) ID hose barb x 0.75-
Hannifin, 125HBL-8-12, fitting or equivalent and installed by plumbing
contractor, typical 1
15
Hose Type: 8-mm (0.31-inch) OD flexible hose supplied with MCS-200/100
16
Hose Type: 9-mm (0.35-inch) ID flexible hose supplied with MCS-200/100
17
Filter* HP recommends 1μm filter for optimal long-term performance of the
MCS-200/100 cartridge or bag filter could be used in a full flow or
side stream flow configuration. Watts FM4X2 stainless steel housing or
equivalent. Provide dielectric unions on both connections. Provide
pleated cartridge rated for 1 μm. Depending on water quality, multiple
units in parallel might be required.
18
Manual air vent Type: 19.05-mm (0.75-inch) two-piece, full-port, brass ball valve with
chrome plated brass ball, PTFE seats, and steel handle, with threaded
connections.
Pressure rating: 600psi WOG, 150psi WSP
Watts® FBV-3C or equivalent
19
Nipple Type: 19.05-mm (0.75-inch) brass close nipple
20
Cap Type: 19.05-mm (0.75-inch) brass cap with chain
Comentários a estes Manuais