Facility planning for implementation 38
The MCS-200/100 has not been certified for seismic environments.
The following table can be used to calculate the weight load of each MCS-200/100 unit, including installed
equipment for proper floor planning.
MCS-100 weight calculation
Component Unit weight Quantity (multiple by) Total weight
MCS-100 (with no server
trays)
670 kg (1479 lb) 1 670 kg (1479 lb)
Component #1: HP
ProLiant SE2x8530a
Gen8 Server Tray*
11.21 kg (24.72 lb) 80 897 kg (1978 lb)
Component #2:
Component #3:
Component #4:
Rack Total:
*Component #1 text included as an example
MCS-200 weight calculation
Component Unit weight Quantity (multiple by) Total weight
MCS-200 (with no hose
kits or IT equipment
installed)
732 kg (1614 lb) 1 732 kg (1614 lb)
Component #1: Mellanox
Infiniband switch*
21.22 kg (46.8 lb) 1 21.22 kg (46.8 lb)
Component #2:
Component #3:
Component #4:
Rack Total:
*Component #1 text included as an example
In the following figure, the load is in the center of the IT racks. Due to adjacency, the leveling feet are
combined to one concentrated weight.