Facility planning for implementation 68
Recommended plumbing configuration for the MCS-200/100
Typical plumbing components for an MCS-200/100 configuration
Item Description Specifications
1
Chilled water return line
Pipe: 31.75-mm (1.25-inch), ASTM B 88, Type L, hard-drawn copper
Fittings: ASTM B16.22 Wrought copper
Solder: ASTM B 32, 95-5 Tin Antimony
Thread sealant: seal and assemble according to local materials and
practices
2
Flow/measurement
balancing valve
Valve type: 31.75-mm (1.25-inch) bronze balancing valve, ball design,
with positive shutoff, integral checked metering ports, adjustable knob,
memory device, calibrated nameplate, integral drain port, and solder
end connections
Position: horizontal run of pipe
Orient drain port toward MCS-200/100. Avoid fittings closer to
measurement valve than five pipe diameters upstream and two pipe
diameters downstream for maximum performance.
Watts CSM-61 or equivalent, typical 1
3
Pipe 31.75 mm (1.25 inches) copper, male (NPT or BSPP) adapter to
connect the MCS-200/100 water hoses, typical 2
4
Isolation valves Valve type: 31.75-mm (1.25-inch), two-piece, full-port, brass ball valve,
with chrome plated brass ball, PTFE seats, steel handle, with female
connections and 31.75-mm (1.25-inch) bushing on the end toward
MCS-200/100 hoses.
Pressure rating: 600 psi WOG, 150 psi WSP
Watts FBV-3C or equivalent
5
Chilled water supply
line
Pipe: 31.75-mm (1.25-inch), ASTM B 88, Type L, hard-drawn copper
Fittings: ASTM B16.22 Wrought copper
Solder: ASTM B 32, 95-5 Tin Antimony
Thread sealant: Seal and assemble according to local materials and
practices