Facility planning for implementation 47
• Flow rate and pressure capacity of chilled water plant input to the design of the facility feed line and
dedicated water loop pipe diameters
• Material compatibility within piping system to minimize the potential for electrochemical corrosion, and
must be corrosion-resistant
• Minimization of elbows and other restrictions that increase flow resistance
• Insulation of piping to minimize risk of condensation and reduce incidental heating of supplied chilled
water
• Availability of a floor drain or reclamation system to capture system condensation
• Structural securing of piping to support weight of distribution network filled with water
• Water quality management, including particulate filtration, treatment, and flushing provisions, with
isolation valves for service requirements
• Availability and access to a data center leak detection system to monitor the infrastructure system for
leaks
• Air vents installed at the highest point in the pipe system
Each MCS-200/100 has an air vent, but additional vents in the supply piping system must be
considered.
HP Water Hook-Up Kit
HP recommends using the MCS-200/100 Water Hook-up Option Kit BW971A, available on the HP website
(http://www.hp.com), to connect the MCS-200/100 to a facility chilled water system. Each kit includes the
hoses and accessories required for connecting the facility supply and return lines to the main inlet and outlet
connections of an MCS-200/100 unit and must be installed prior to the delivery of an MCS-200/100.
MCS-200/100 Water Hook-Up Option Kit contents
Item Description (quantity)
1
Main hose assembly* (2)
2
90-degree elbow assembly (2)
3
Teflon gasket (2)