Facility planning for implementation 50
Above the unit
An HP Water Hook Up Kit must be installed prior to activating an MCS-200/100. The kit contains
approximately 350 cm (138 inches) of flexible hose with terminated fittings on each end. The length that is
available outside the MCS-200/100 depends on the preferred type of connection.
Available hose lengths outside the MCS-200/100 by connection type
Connection type
Approximate length supply
hose
Approximate length return hose
Bottom
280 cm (110 inches) 300 cm (118 inches)
Rear
280 cm (110 inches) 300 cm (118 inches)
Top
200 cm (79 inches) 180 cm (71 inches)
The following figure shows the location of the condensate and overflow in the rear of the cooling unit. The
MCS-200/100 includes both tubes for the hookup. Each tube is approximately 3 m (9 ft) in length. The
overflow hose has an inner diameter of 9 mm (0.35 inch) and the condensation hose has an outer diameter