Facility planning for implementation 79
Be sure facility managers understand that additional load is being added to the facility water supply. Be
aware that the heat load being added might have an effect on other components being cooled by the
facility water plant.
CAUTION: The water supply system feeding the MCS-200/100 must be capable of withstanding
deadheading (operating with a closed line) and operation with rapid and frequent changes in
flow requirements, including long periods with zero water flow.
Plumbing materials to avoid
Do not use the following materials with a closed water system:
Oxidizing biocides
High zinc and brass components
Non-stainless steel iron components
Environmental considerations
Parameter Value
Room temperature
Recommended
minimum/maximum
Allowable minimum/maximum
18°C(64.4°F)/27°C(80.6°F)
15°C (59°F)/32°C(90°F)
Humidity:
Recommended minimum
Recommended maximum
Allowable range
5.5°C (41.9°F) dew point
60% relative humidity and 15°C (59°F) dew point
20%–-80%
The temperatures stated are for an elevation of 0 to 5000 ft above sea level. The maximum operating
temperatures must be de-rated by 1ºC per 1000 ft for locations 5000 to 10,000 ft above sea level.
Control system
The MCS-200/100 includes a control system that constantly monitors the air temperatures, water
temperatures, and flow rate. The management module attempts to maintain the air temperature at the target
set point. If the set point temperature cannot be maintained, the HP Modular Cooling System 200/100
management module will generate an alarm and notify facility management systems, as configured.
For site evaluations and technical consulting services for your site, see the HP Modular Cooling System
200/100 User Guide.
Before installing and running active components
CAUTION: If the MCS-200/100 unit runs in manual mode for a period of time without an
adequate heat load being generated by servers or other computing/networking devices, excess
condensation could occur within the cabinet or system.
Prior to starting up any active components mounted in the MCS-200/100 rack, such as servers, storage
devices, and so on, the following actions must be performed: