Overview 18
Parameter
Packaged system (as
shipped on pallet)
Unpackaged system
(off pallet, unwrapped)
Unpackaged CTO system
Height
2159 mm (85 inches) 2007 mm (79 inches) 2007 mm (79 inches)
Width
914.4 mm (36 inches) 600 mm (23.6 inches) 600 mm (23.6 inches)
Depth
1727 mm (68 inches) 1200 mm (47.2 inches) 1200 mm (47.2 inches)
265 kg (584 lb)
1
135 kg (299 lb)
2
1042 kg (2297 lb)
3
MCS-200 (single rack configuration) physical specifications
Parameter
Packaged system (as
shipped on pallet)
Unpackaged system
(off pallet, unwrapped)
Unpackaged CTO system
Height
2285 mm (90 inches) 2007 mm (79 inches) 2007 mm (79 inches)
Width
1219 mm (48 inches) 904 mm (35.6 inches) 904 mm (35.6 inches)
1829 mm (72 inches) 1510 mm (59.5 inches) 1510 mm (59.5 inches)
Weight
732 kg (1614 lb)
1
478 kg (1054 lb)
2
1521 kg (3353 lb)
3
MCS-200 expansion rack physical specifications
Parameter
Packaged system (as
shipped on pallet)
Unpackaged system
(off pallet, unwrapped)
Unpackaged CTO system
Height
2159 mm (85 inches) 2007 mm (79 inches) 2007 mm (79 inches)
Width
914.4 mm (36 inches) 600 mm (23.6 inches) 600 mm (23.6 inches)
Depth
1727 mm (68 inches) 1399 mm (55.1 inches) 1399 mm (55.1 inches)
Weight
308 kg (680 lb)
1
179 kg (395 lb)
2
1222 kg (2694 lb)
3
1 Weight for a completely packaged system with unpopulated server rack
2 Weight for an unpackaged system with unpopulated server rack
3 Approximate weight for an unpackaged CTO system (actual weight varies, according to configuration)
If the top shipping bracket interferes with deploying the MCS-200/100, it can be removed. With the top
shipping bracket, the total height of the unpackaged system is 2069 mm (81.5 inches).
Electrical specifications
The following table lists the electrical specifications for the MCS-100 unit.
Parameter Value Comments
Operating voltage
230 VAC +/- 10%, 50 Hz
208 VAC +/- 10%, 60 Hz
—
AC line phase
Single —
Maximum input current
18 A Per line cord
Maximum inrush current
200 A Per line cord
Dropout/hold-up time at
minimum line voltage
20 ms —
Transfer time of AC transfer
switch
2 s —
Circuit breaker rating
LAHJ Per cord
Power factor
> 0.95 At all loads
Ground leakage current
< 19.4 mA Per line cord
Comentários a estes Manuais