HP Modular Cooling System Guia de Início Rápido Página 67

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 93
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 66
Facility planning for implementation 67
Recommended floor cutouts (dual rack configuration)Option 8 (MCS-200 cooling unit side and rear flush to
tile)
A wider opening in the back of the IT rack is optional with MCS-200. The floor tile sizes used in the above
options are 600 mm x 600 mm (23.6 inches x 23.6 inches). Floor tile sizes vary. The allowable tolerances
are +/- 3.2 mm (+/- 0.125 inch). When installing multiple MCS-200/100 units in a row, you must consider
the tolerances as you plan the cutouts.
Chilled water system components
Chilled water supply and return service are required for each MCS-200/100 in order to have a particular
combination of components for peak performance. These components are identified in the following figures
and tables. Components drawn with a solid line are strongly recommended. Components drawn with dotted
lines are advisable for a higher availability and serviceability.
Vista de página 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 92 93

Comentários a estes Manuais

Sem comentários